Tesenso M-Bus LoRaWAN
Product Datasheet
Device Profile for Tesenso IoT Cloud
Decoder/Payload Converter for Tesenso IoT Cloud
Tesenso IoT Cloud Converter Template
Attributes for correct values
In order to proccess the rawPayload of the Tesenso M-Bus device, please make sure that you add to each device a server attributes "scale":
Uplink documentation
meter values are sent are sent on Port 2
sample Uplink message
on request - contact us via https://www.tesenso.com/contact
Downlink documentation
All Downlinks shall be sent on Port 3
Class should be set to C
Downlink samples
Add secundary adress manually to EEPROM
Name: | Length | MsgType | ID | |||
---|---|---|---|---|---|---|
Unit: |
| Enum | BCD encoded | |||
Bytes | 1 | 1 | 1 | 1 | 1 | 1 |
Range: | 5 | 133 | HighByte | LowByte |
05 --> Length
85 --> MsgType
17670401 --> secondaryAdress of the meter
Downlink for Scan M-Bus slave on the M-Bus
Name: | Length | MsgType | Retry |
---|---|---|---|
Unit: |
| Enum |
|
Bytes | 1 | 1 | 1 |
Range: | 2 | 130 | 0..3 |
02 --> Length
82 --> MsgType
01 --> Retry
Delete saved slaves from EEPROM
Name: | Length | MsgType |
---|---|---|
Unit: |
| Enum |
Bytes | 1 | 1 |
Range: | 1 | 131 |
01 --> Length
83 --> MsgType
Change send Intervall:
Message Types | ||||||
---|---|---|---|---|---|---|
Name: | Length | MsgType | Flags | status msg interval | Meter interval | |
Unit: |
| Enum |
| Min(s) | Min(s) | |
Bytes | 1 | 1 | 1 | MSB | LSB | 1 |
Range: | 0..255 | 128 |
sample downlinks to change the intervall:
05800000001E --> 30 minutes
05800000000F --> 15minutes
058000000005 --> 5minutes
Last updated