Ambiance Monitor
Last updated
Last updated
Product Datasheet
Battery voltage
batteryVoltage
telemetry
float
Air temperature
temperature
telemetry
float
Air humidity
humidity
telemetry
float
Barometric pressure
barometricPressure
telemetry
integer
CO2 concentration
co2
telemetry
integer
PIR sensor: activity counter
motion
telemetry
integer
Gas sensor: total VOC
voc
telemetry
integer
Header
Version
uint8
Header
Device ID
uint16
Header
Flags
uint16
Sensor 0
Battery voltage
uint16
x / 1000
V
Sensor 1
Air temperature
uint16
x / 65535 ∙ 175 − 45
°C
Sensor 1
Air humidity
uint16
x / 65535 ∙ 100
%
Sensor 2
Barometric pressure
uint16
x ∙ 2
Pa
Sensor 3
Ambient light CH0 (visible + infrared)
uint16
x
Sensor 3
Ambient light CH1 (infrared)
uint16
x
Sensor 4
CO2 concentration
uint16
x - 32768
ppm
Sensor 4
CO2 sensor status
uint16
x
Sensor 4
Raw IR reading
uint16
x
Sensor 5
PIR sensor: activity counter
uint16
x
Sensor 6
Gas sensor: total VOC
uint16
x
ppb
02
Version
2
0bbd
Device ID
3005
007f
Flags
0b0000000001111111
0b92
Battery voltage
2.96
V
6a51
Air temperature
27.68
deg
5d48
Air humidity
36.44
%
bc4e
Barometric pressure
96412
Pa
0262
Ambient light CH0
610
0069
Ambient light CH1
105
81c7
CO2 concentration
455
ppm
0000
CO2 sensor status
0
93d4
Raw IR reading
37844
000b
PIR activity counter
11
0111
Gas sensor: total VOC
273
ppb
Illuminance
679
lx
02
Version
2
0bbd
Device ID
3005
0001
Flags
0b0000000000000001
0b92
Battery voltage
2.96
V
set period
0x0001
Set sampling period in seconds (1...65535).
≥ 0.2.7
set period + save
0x0002
... + save settings
≥ 0.2.7
set dr
0x0003
Set default TX data rate. Used for next TX. Actual data rate for following TX may vary, if ADR is enabled.
≥ 0.2.7
set dr + save
0x0004
... + save settings
≥ 0.2.7
set adr on
0x0005
Enable ADR.
≥ 0.2.7
set adr on + save
0x0006
... + save settings
≥ 0.2.7
set adr off
0x0007
Disable ADR.
≥ 0.2.7
set adr off + save
0x0008
... + save settings
≥ 0.2.7
set dr_min
0x0009
Set minimum data rate (dr_min overrides ADR settings)
≥ 1.2.0
set dr_min + save
0x000A
... + save settings
≥ 1.2.0
set dr_max
0x000B
Set maximum data rate (dr_max overrides ADR settings)
≥ 1.2.0
set dr_max + save
0x000C
... + save settings
≥ 1.2.0
set pwridx_min
0x000D
Set minimum TX power index (overrides ADR settings)
≥ 1.2.0
set pwridx_min + save
0x000E
... + save settings
≥ 1.2.0
set pwridx_max
0x000F
Set maximum TX power index (overrides ADR settings)
≥ 1.2.0
set pwridx_max + save
0x0010
... + save settings
≥ 1.2.0
set send_period
0x0011
Set send period. Examples: 0 or 1: send after every sampling. 4: send after every fourth sampling.
≥ 1.4.0
set send_period + save
0x0012
... + save settings
≥ 1.4.0
set join_period
0x0013
Set re-join period in hours (0... 1000). Examples: 24: re-join network every 24 hours. 0: never re-join
≥ 1.4.2
set join_period + save
0x0014
... + save settings
≥ 1.4.2
set pwridx
0x0015
Set default TX power index. Used for next TX. Actual pwridx for following TX may vary, if ADR is enabled.
≥ 1.4.5
set pwridx + save
0x0016
... + save settings
≥ 1.4.5
set linkcheck_period
0x0017
Set link check period (default: 36)
≥ 1.5.0
set linkcheck_period + save
0x0018
... + save settings
≥ 1.5.0
set linkcheck_tolerance
0x0019
Set link check period (default: 6)
≥ 1.5.0
set linkcheck_tolerance + save
0x001A
... + save settings
≥ 1.5.0
set linkcheck_limit
0x001B
Set link check limit (default: 12)
≥ 1.5.0
set linkcheck_limit + save
0x001C
... + save settings
≥ 1.5.0
set port
0x001D
Set LoRaWAN uplink port (1...223, default: 1)
≥ 1.6.0
set port + save
0x001E
... + save settings
≥ 1.6.0
set param 0 set param 1 ... set param 15
0x0020 0x0021 ... 0x002F
Set device specific parameter 0. Range: 0...65534; 65535: parameter is ignored. Set device specific parameter 1 ... Set device specific parameter 15
≥ 1.4.0
set sensor_period 0 set sensor_period 1 ... set sensor_period 9
0x0050 0x0051 ... 0x0059
Set (sub-)sampling period of sensor 0 Set (sub-)sampling period of sensor 1 ... Set (sub-)sampling period of sensor 9
≥ 1.4.5
set sensor_period 0 + save set sensor_period 1 + save ... set sensor_period 9 + save
0x0060 0x0061 ... 0x0069
... + save settings
≥ 1.4.5
reset
0xFEFE
Reset device. Unsaved parameter changes are lost.
≥ 0.2.7
factory reset
0xFEF0
Erase settings in flash and reset
≥ 0.2.7
sleep
0xFEF1
Enter sleep mode (power off)
≥ 1.5.0
set period 60 seconds + save
0002003CF5A1
set dr 2 + save
0004000224C0
set send_period 20 + save
001200142EA0
reset
FEFE00003C50
factory reset
FEF00000FF31