Pulse V4

Product Datasheet

Software

First to do:

  • Activate the Device: --> Connect the Device via an USB data cable.

  • Start the Adeunis IoT Software from your computer

  • Set the sampling period to 1800 = Update all 1 hours / 3600 = all 2 hours

  • Flow calculation let it standard: 60

  • Type: other

  • Activate the Timestamp Configuration (no piucture)

  • Update the Time under Advanced

Printscreen IoT software Adeunis

Installation

Caution

Before installation of the device, make sure, that you ground yourself. Otherwie the Device can shut down or even break.

From the document: PULSE_V4-Technical_Reference_Manual_APP_2.1-22.02.2021.pdf

Example downlink:

Warning: the value set is incorrect -> 15630916 = EE8244 so-> 00EE8244 8 digits fill up with 0

Converter: https://www.matheretter.de/rechner/zahlenkonverter Dezimal to Hexadezimal

4117000000011700EE8244 is the correct DL with your value

Downlink Port 1

___________________________________________________________________________________

The DL for moditying the registers is 0x41, to be sent to port 1

To change the initial index value of a pulse, first set it to a different pulse value and then enter the set value. The DLs are as follows, depending on your

requirements

Channel A only: 41170000000117XXXXXXXX

Channel B only : 41180000000 118X0X0XXXXX

Canal A+ Canal B: 41170000000117XXXXXXXX180000000118XXXXXXXX

00000001 = Different index values at 1 pulse, for example

XXXXXXXX = value of the index to be integrated, coded in hexadecimal

The two values (00000001 et XXXXXXXX) are different

After the downlink 0x41 is sent, the associated uplink 0x33 is immediately returned. If the update of the register(s) was successful, the device will

perform a backup and automatically begin its restart procedure. In addition, the Config bit of the status byte will be set to 1 in the next scheduled uplink

irame (periodic, alarm or keep-alive frame) if all has gone well

To help you, please find below the MRT

Warning: once this DL is used, the value read locally on the loT configurator will be equal to 0